Interactive P/T Chart
Refrigerant Pressure Temperature Chart
Compare saturation pressure vs temperature for common HVAC refrigerants. Toggle between °F/PSIG and °C/kPa. Select multiple refrigerants for comparison.
Select Refrigerants:
Units:
| Temp (°F) | R-410A PSIG | R-22 PSIG |
|---|---|---|
| 20°F | 57.5 | 24 |
| 30°F | 74.6 | 30.1 |
| 40°F | 94.3 | 37 |
| 50°F | 117.2 | 44.9 |
| 60°F | 143.6 | 53.7 |
| 70°F | 174 | 63.8 |
| 80°F | 208.4 | 74.9 |
| 90°F | 247.6 | 87.3 |
| 100°F | 291.6 | 101 |
| 110°F | 340.7 | 116.2 |
| 120°F | 395.3 | 132.9 |
| 130°F | 455.7 | 151.2 |
| 140°F | 522.2 | 171.4 |
Note: These are saturated vapor pressures at sea level. Actual pressures may vary based on altitude, refrigerant purity, and equipment design. R-454B and R-32 are mildly flammable (A2L class).
Understanding Pressure-Temperature Relationships
Why P/T Charts Matter
The pressure-temperature (P/T) relationship is fundamental to HVAC diagnostics. At any given temperature, a refrigerant in a saturated state will have a specific pressure. This relationship allows technicians to:
- Determine superheat and subcooling values
- Diagnose system charge issues
- Verify proper system operation
- Troubleshoot evaporator and condenser problems
Common Refrigerant Comparisons
| Refrigerant | Pressure @ 70°F | Application | GWP |
|---|---|---|---|
| R-410A | 174 PSIG | Residential A/C, Heat Pumps | 2088 |
| R-22 | 64 PSIG | Legacy Systems | 1810 |
| R-134a | 40 PSIG | Automotive, Medium Temp | 1430 |
| R-404A | 136 PSIG | Commercial Refrigeration | 3922 |
| R-454B | 159 PSIG | R-410A Replacement (2025+) | 466 |
How to Use This Chart
- Select the refrigerant(s) you're working with
- Find the current temperature of your evaporator or condenser
- Read the corresponding saturation pressure
- Compare to your gauge readings to calculate superheat/subcooling